Lightning Risk in Data Centers: Designing a Consistent Site-Wide Protection System
A data center houses sensitive equipment and functions whose availability depends on several networks: power, telecommunications, automation, cooling, and security. A direct lightning strike can damage the structure or outdoor facilities; induced or conducted surges can also affect electronic equipment. Protection must therefore be considered at the site level and not just for the roof.
Start with a risk analysis
The geometry of buildings, local lightning strike density, access points, roof equipment, and incoming power lines all influence the protection strategy. The analysis must identify potential consequences for personal safety and business continuity. Applicable standards, notably IEC 62305 for analysis and design based on specific configurations and NF C 17-102 for devices with a lightning arrestor (PDA) when such devices are selected, must be properly distinguished.
Current collection, down conductors, and grounding form a single system
A lightning rod serves as a preferred point of attraction, but it does not protect the installation on its own. Down conductors carry the current to the ground electrode; their placement and the management of separation distances help limit dangerous discharges. The electrical continuity of the connections, joints, and grounding system must be analyzed in conjunction with the building’s metal structures.
Lightning rods and surge protectors do not serve the same purpose
External protection is designed to address direct strikes and the flow of lightning current. Surge arresters, installed at various levels of the facilities, limit certain transient overvoltages on power networks and signal lines. Coordinating surge arresters with control panels and sensitive equipment is essential to ensure that a properly designed external protection system does not leave any internal vulnerabilities unaddressed.
Protection of Technical Roofing Equipment
Cooling units, control cabinets, piping systems, cable trays, and metal supports must be included in the protection plan. Any protection zones must be calculated based on the selected method and level; they cannot simply be derived from a single radius listed in a catalog. Maintenance procedures must also provide for inspections following significant events.
The Case of Early-Ignition Devices
ABB HELITA® PULSAR uses spark-gap lightning protection technology. The product line is available with spark-gap response times of 30, 45, and 60 microseconds and a protection radius of up to 107 m, depending on the model, protection level, and installation height. The RodCheck system provides a visual indication after a strike to guide equipment inspection; it does not replace a comprehensive inspection of the entire protection system.
Documenting Controls Over Time
Protective systems remain vulnerable to aging, changes to the building, and work performed on the roof. As-built drawings, ground measurements, inspections of connections, and monitoring of protective systems must be kept up to date. A data center expansion or the addition of equipment on the roof warrants a reassessment of the protective system.
Lightning protection for critical infrastructure is, above all, a coordinated effort: risk analysis, external protection, equipotential bonding, surge protection, and maintenance must form a coherent system.